KV10 – LCGK VFD https://m.vfdmanufacturer.com Reliable VFD & Solar Solutions for Industry and Irrigation Thu, 26 Jun 2025 04:01:14 +0000 en-US hourly 1 https://wordpress.org/?v=6.8.2 https://m.vfdmanufacturer.com/wp-content/uploads/2025/02/cropped-kuvo-logo-32x32.png KV10 – LCGK VFD https://m.vfdmanufacturer.com 32 32 KV10 series Variable Frequency Drive https://m.vfdmanufacturer.com/product/kv10/ Mon, 31 Mar 2025 04:02:49 +0000 https://m.vfdmanufacturer.com/?post_type=products&p=999
InputInput Voltage200V(-10%) ~ 240V(+10%) Single-phase
380V(-10%) ~ 480V(+10%) Three-phase
Input Frequency50 ~ 60Hz
OutputControl MethodVF Control
Frequency Range0 ~ 300Hz
Frequency Resolution0.1Hz
Output Voltage0 ~ Input Voltage
Carrier Frequency1 ~ 10kHz
Speed Regulation Range1:50
Overload Capacity150% rated current for 1 minute
Control FeaturesTorque Boost0.0% ~ 30.0%
Acceleration/Decel Time0.0 ~ 6553.5 s
VF Curve Modes0: Multi-point V/F
1: 2.0-exponent Curve
2: 1.7-exponent Curve
3: 1.2-exponent Curve
Jog ControlJog frequency range: 0.00Hz~5.00Hz
Jog acceleration/deceleration time: 0.0s~600.0s
DC BrakingBraking Frequency: 0.00Hz ~ Max Frequency
Braking Time: 0.0s ~ 60.0s
Braking Current: 0.0% ~ 100.0%
Dynamic BrakingBuilt-in Braking Unit (Optional)
Energy Consumption Braking Ratio: 0.0% ~ 100.0%
Advanced Functions​Built-in PIDEnables closed-loop process control systems (e.g., constant pressure, temperature control) through real-time feedback adjustment
Built-in Multi-Speed & Simple PLCSupports up to 16 preset speed segments via internal PLC programming or external control terminals
Programmed Acceleration/Deceleration TimesProvides 4 independent acceleration/deceleration time groups for flexible operation mode selection. Typical applications include staged startup/shutdown and load-adaptive speed regulation
ProtectionsOverheat/Overload/Overcurrent/Overvoltage/Stall Prevention/Short Circuit Protection
Swing Frequency ControlSwing Frequency Control (Textile Industry Applications)
Fixed-Length ControlFixed-length Control
Frequency ReferenceDigital Panel/Analog Input/Communication/PID
Command SourcesPanel Operation/Terminal Control/Communication
FieldbusRS485 Interface (MODBUS-RTU Protocol)
​InstallationInstallationSupport wall-mounted
Protection classIP20
Working  temperature-10℃~+50℃; after exceeding 40℃, the derating will be reduced by 2% according to 1℃.
Cooling methodForced air cooling
Humidity20%~95%RH(condensation free)
Installation environmentLess than 1000m; after exceeding 1000m, the amount will be reduced by 1% according to 100m.
]]>